UL 1561 covers dry-type power transformers and general-purpose transformers rated 600 V or less with a capacity greater than 10 kVA. UL 1562 covers dry-type transformers rated above 600 V. The two standards are divided by voltage class, not simply by capacity.
Under SINCRON file number E549596, the 10–1,000 kVA range corresponds to UL 1561, while the 1,250 / 1,500 / 2,000 / 2,500 / 3,000 kVA range corresponds to UL 1562. A single file number covering multiple capacity ranges reduces the cost of coordinating interfaces and documentation across multiple suppliers.
| Capacity range | Applicable standard | Typical applications |
|---|---|---|
| 100 VA–10 kVA | UL 5085-1/5085-2 | Control transformers, equipment-mounted auxiliary use |
| 10–1,000 kVA | UL 1561 | Data centers, commercial buildings, medical facilities, energy storage systems |
| 1,250–3,000 kVA | UL 1562 | Campus main distribution, main step-down for AI computing centers |
UL 1562 is defined by a rated voltage above 600 V, not by a capacity above 1,000 kVA. During selection, confirm the site voltage scheme first and then match the capacity range. If a project involves both sub-600 V distribution and high-voltage main transformers, confirm that both ranges are covered under the same file number.
They are divided by rated voltage: UL 1561 applies to ≤600 V and UL 1562 to >600 V. Capacity ranges are a supporting engineering reference, not the classification criterion.
Yes. SINCRON file number E549596 covers three levels of standards at once: UL 5085-1/5085-2, UL 1561, and UL 1562.
Log in to UL Product iQ, enter E549596, check the certificate holder and the product category Power and General-purpose Transformers, Dry Type, and compare the covered model pages.