Figure: SINCRON UL/cUL Listed dry-type isolation transformer, suitable for semiconductor production line power distribution applications.
Washington State is home to semiconductor manufacturing and related industries. Process equipment and test instruments in cleanrooms typically require stable 208Y/120 V distribution, while plant incoming supply is mostly 480 V Delta. Dry-type isolation transformers are used for voltage conversion and neutral grounding reconfiguration.
Semiconductor production lines are sensitive to power disturbances; at equipment entry acceptance, not only are nameplate parameters checked, but certification documents must also be consistent with file records. Electrostatic shielding and full-unit Listing are common procurement conditions for such projects.
A semiconductor supporting company in Washington needed to convert the plant's 480 V Delta distribution to 208Y/120 V for process equipment during a production line expansion, and required the equipment to have verifiable full-unit Listing and a low-interference design.
The UL/cUL full-unit Listed dry-type isolation transformer supplied by SINCRON was configured to the project-specified system, with the following specifications:
| Item | Specification |
|---|---|
| Input Voltage | 480 V Delta |
| Output Voltage | 208Y/120 V |
| Capacity | 300 kVA |
Under file number E549596, dry-type transformers with a rated voltage up to 600 V and a capacity greater than 10 kVA fall within the scope of the UL 1561 standard; 300 kVA falls within this range.
File number E549596 can be verified on the UL Product iQ platform (productiq.ulprospector.com), checking the certificate holder 'SHENZHEN XINGKERONG TECHNOLOGY CO., LTD.' and the product category Power and General-purpose Transformers, Dry Type.
An electrostatic shield is placed between the primary and secondary windings to suppress common-mode interference and N-PE interference from entering process equipment circuits, making it suitable for cleanroom environments sensitive to power quality.
Before leaving the factory, the equipment completed insulation withstand voltage, temperature rise, load and aging tests in accordance with full-unit Listing requirements, and was accompanied by a certification document package and verification materials for the general contractor and supervisor to check at the entry stage. On-site verification is based on the consistency of the UL Product iQ file record, nameplate information and accompanying documents.
Process equipment and test instruments are sensitive to common-mode interference; an electrostatic shield can suppress interference from coupling into load circuits through the windings, and together with isolation and grounding reconfiguration it improves power quality.
Under file number E549596, dry-type transformers with a rated voltage up to 600 V and a capacity greater than 10 kVA fall within the scope of UL 1561, and 300 kVA falls within this range.
Full-unit Listing means the equipment as a whole passes type tests and a factory audit; component recognition covers only the component level, and on-site acceptance usually accepts only the former.
For the selection of power distribution equipment for semiconductor production lines, voltage system matching, interference suppression capability and verifiable certification are equally important. Relying on full-unit Listed products under file number E549596, SINCRON provides verifiable dry-type isolation transformer options for precision manufacturing applications in North America.
Mike