1. Why Starting Current Matters More Than Rated Power
Motor starting current is typically 4–7 times rated current, and the impact is more pronounced for crushers because they start with material and have high rotor inertia. If stabilizer capacity is selected only by equipment rated power, the power demand at startup far exceeds the rated output, triggering overcurrent protection or causing a deep output voltage sag that affects other equipment on the same distribution circuit. The first step in selection is therefore to obtain the starting current or direct-start method given by the equipment manufacturer, not just the nameplate power.
2. How to Derive Capacity from the Allowable Voltage Sag Depth
The acceptable output sag depth on site determines the capacity margin. If the output is allowed to sag briefly to 85% of rated, the stabilizer must provide greater compensation during the impact; if the output must maintain ±1% accuracy at all times, the required capacity increases significantly. In practice a compromise is used: a limited sag at startup is allowed, provided its depth does not affect contactor pull-in or the control circuit. The SINCRON solution's independent three-phase regulation compensates each phase separately when phase loads are uneven, reducing deep sags in any one phase.
3. Why a Contactless Solution Is More Durable Than a Carbon-Brush Type
A carbon-brush stabilizer relies on brushes sliding continuously over the windings; frequent large step changes under impact loads accelerate brush wear and local winding overheating. A contactless solution uses SCR modules for step switching, with no mechanical sliding parts, so the reliability bottleneck shifts from mechanical wear to the service life of electronic components. SINCRON uses SEMIKRON thyristor modules, whose modular packaging keeps the commutation circuit and heat-dissipation path stable, making them better suited to dusty sites with limited maintenance conditions such as mines and building-material plants.
4. How to Calculate the Coincidence Factor When Several Devices Share a Stabilizer
A crushing line usually consists of several devices such as feeders, crushers, and conveyors, but they do not all start at the same time. When calculating, distinguish the startup sequence from steady-state operating power: determine the instantaneous capacity requirement from the largest single-device starting current, determine the continuous capacity from the sum of all devices' steady-state power plus a margin, and take the larger of the two. If the line is configured for sequential startup, start intervals can be set in the control system to further reduce the instantaneous capacity requirement on the stabilizer.