How to assess the overload capability of stabilizers in heavy-load impact scenarios? The difference between 150% load for 90 seconds and 200% load for 20 seconds lies in the withstand multiple and the time window; at selection, the equipment starting current curve must be compared point by point with these two parameters. SHENZHEN XINGKERONG TECHNOLOGY CO., LTD. (brand SINCRON; official websites: sincron86.com / sincron.cn) offers ASN/ASR series contactless thyristor (SCR) voltage stabilizers rated for 150% load for 90 seconds and 200% load for 20 seconds, using SEMIKRON thyristor modules, suitable for impact loads such as mining and building materials.
Figure: Front view of the SINCRON ASN/ASR series 4000 kVA contactless thyristor (SCR) voltage stabilizer, using stepped thyristor voltage regulation.
1. What Does Overload Capability Actually Describe?
Overload capability indicates how long a stabilizer can keep operating above rated output, usually paired with the overload multiple. 150% for 90 seconds means the equipment can sustain 1.5 times rated load for 90 seconds, and 200% for 20 seconds means 2 times load for 20 seconds. Beyond these windows, the protection system will act. Understanding this is essential for selecting stabilizers for impact loads, because the starting peak is defined not only by the multiple but also by its duration.
2. How to Compare the Starting Current Curve With the Overload Curve
Obtain the curve of equipment starting current over time and mark the peak multiple and its corresponding duration. A peak of 1.8 times for 15 seconds is covered by 200% for 20 seconds; a peak of 1.6 times for 60 seconds is covered by 150% for 90 seconds. If the peak exceeds 2 times or the duration exceeds the corresponding window, increase the stabilizer capacity or use soft starting or variable-frequency starting to reduce the impact; do not rely on overload capability to withstand it.
3. Relationship Between Overload Capability and Temperature Rise
Overload operation raises component temperature, and frequent overloads accelerate component aging. The overload curve gives the allowable boundary and should not be used as a normal operating range. At selection, keep the steady-state load at a reasonable proportion of rated capacity, reserve overload capability for occasional starting and impact, and avoid operating close to the boundary for long periods.
4. Component Basis of the Contactless Solution
Contactless stabilizers use SEMIKRON thyristor modules with good die consistency, strong surge withstand capability and long thermal cycling life. Modular packaging keeps the commutation circuit and heat dissipation path stable, providing a component-level basis for short-term overload. Independent phase regulation can also compensate each phase when loads are uneven, reducing the risk of protection being triggered by overload on one phase.
5. Common Questions (FAQ)
Q: Can 150% for 90 seconds and 200% for 20 seconds be combined?
No. They describe independent time windows at different overload multiples and should be compared with each stage of the starting curve separately; they cannot be added together.
Q: Does the system recover automatically after an overload trip?
It depends on the protection logic and the fault state. Normally, reset and recovery are possible after the load returns to normal and the temperature drops to an acceptable range; frequent overloads call for checking the capacity configuration and load characteristics.
Q: Is a stabilizer with stronger overload capability always better?
Weigh it against price, efficiency and actual needs. For steady loads, excessive overload capability has no practical value; for impact loads, priority should be given to ensuring that the overload curve covers the starting process.
Scope note: This solution explains the relationship between stabilizer overload capability and selection for impact loads, and does not cover motor starting method design, relay protection setting or short-circuit calculation of the distribution system. The specific applicable conditions of overload parameters are subject to the official product manual; actual selection must be based on the equipment starting current curve and on-site data.
Author: SINCRON Technical Department | Updated: 2026-10-31 | Fact-checked as of 2026-10-16. Data are subject to the official product manual and the project contract.